Standards and guidance
The standards a lighting scheme is designed to, in plain terms.
Which standards apply
BS EN 12464-1
Illuminance, uniformity, glare and colour rendering for each task and area indoors.
BS EN 12464-2
The same for yards, loading areas, car parks and external plant.
BS 5266-1
Where emergency lighting is needed and how it is designed, tested and recorded.
BS EN 1838
The illuminance, response time and duration that escape lighting has to achieve.
Approved Document L, Volume 2
Minimum efficacy and controls for new and replacement lighting.
BS EN 15193-1
The method for calculating LENI, the annual lighting energy per square metre.
SLL Code for Lighting and Lighting Guides
Recommended practice by building type, including LG1 industrial, LG5 education and LG7 offices.
ILP Guidance Note 1
Limits on sky glow, light spill and glare from exterior lighting, by environmental zone.
HSG38
Guidance on the legal duty to provide suitable and sufficient lighting in every workplace.
Light levels by sector
Every task has a required light level, uniformity, glare limit and colour rendering. Open a sector to see its figures.
Offices500 lux at the desk, glare limited to UGR 19
| Task or area | Lux | UGR limit | Uniformity | Ra |
|---|---|---|---|---|
| Filing, copying | 300 | 19 | 0.40 | 80 |
| Writing, typing, reading, data processing | 500 | 19 | 0.60 | 80 |
| CAD workstations | 500 | 19 | 0.60 | 80 |
| Technical drawing | 750 | 16 | 0.70 | 80 |
| Conference and meeting rooms | 500 | 19 | 0.60 | 80 |
| Reception desk | 300 | 22 | 0.60 | 80 |
| Archives | 200 | 25 | 0.40 | 80 |
Retail and showrooms300 lux on the sales floor, colour rendering of 80 or better
| Task or area | Lux | UGR limit | Uniformity | Ra |
|---|---|---|---|---|
| Sales area | 300 | 22 | 0.40 | 80 |
| Till area | 500 | 19 | 0.60 | 80 |
| Wrapper table | 500 | 19 | 0.60 | 80 |
Education300 lux in classrooms, 500 lux at the board
| Task or area | Lux | UGR limit | Uniformity | Ra |
|---|---|---|---|---|
| Classrooms, tutorial rooms | 300 | 19 | 0.60 | 80 |
| Classrooms for evening classes and adult education | 500 | 19 | 0.60 | 80 |
| Black, green and white boards | 500 | 19 | 0.70 | 80 |
| Lecture halls | 500 | 19 | 0.60 | 80 |
| Circulation areas, corridors | 100 | 25 | 0.40 | 80 |
| Stairs | 150 | 25 | 0.40 | 80 |
Warehousing and logistics150 lux in manned aisles, with light on the rack face
| Task or area | Lux | UGR limit | Uniformity | Ra |
|---|---|---|---|---|
| Store and stock rooms | 100 | 25 | 0.40 | 60 |
| Dispatch, packing and handling areas | 300 | 25 | 0.60 | 60 |
| Storage rack areas: gangways, unmanned | 20 | none | 0.40 | 40 |
| Storage rack areas: gangways, manned | 150 | 22 | 0.40 | 60 |
| Storage rack areas: control stations | 150 | 22 | 0.60 | 80 |
| Loading ramps and bays | 150 | 25 | 0.40 | 40 |
Manufacturing and assembly200 to 750 lux, set by the finest task on the line
| Task or area | Lux | UGR limit | Uniformity | Ra |
|---|---|---|---|---|
| Rough assembly work | 200 | 25 | 0.60 | 80 |
| Medium assembly work | 300 | 25 | 0.60 | 80 |
| Fine assembly work | 500 | 22 | 0.60 | 80 |
| Precision assembly work | 750 | 19 | 0.70 | 80 |
| Welding | 300 | 25 | 0.60 | 60 |
| Rough and average machining, tolerances of 0.1 mm or more | 300 | 22 | 0.60 | 60 |
| Precision machining and grinding, tolerances under 0.1 mm | 500 | 19 | 0.70 | 60 |
| Scribing, inspection | 750 | 19 | 0.70 | 60 |
Food and drink production200 to 500 lux, in sealed and cleanable fittings
| Task or area | Lux | UGR limit | Uniformity | Ra |
|---|---|---|---|---|
| Washing, barrel filling, cleaning, sieving, peeling | 200 | 25 | 0.40 | 80 |
| Sorting and washing of products, milling, mixing, packing | 300 | 25 | 0.60 | 80 |
| Cutting and sorting of fruit and vegetables | 300 | 25 | 0.60 | 80 |
| Critical zones in slaughterhouses, butchers and dairies | 500 | 25 | 0.60 | 80 |
| Manufacture of delicatessen foods, kitchen work | 500 | 22 | 0.60 | 80 |
| Product control, inspection of glasses and bottles | 500 | 22 | 0.60 | 80 |
| Colour inspection | 1,000 | 16 | 0.70 | 90 |
Yards and loading bays5 to 50 lux outdoors, by type of traffic
| Task or area | Lux | GR limit | Uniformity | Ra |
|---|---|---|---|---|
| Walkways exclusively for pedestrians | 5 | 50 | 0.25 | 20 |
| Traffic areas for slowly moving vehicles, up to 10 km/h | 10 | 50 | 0.40 | 20 |
| Regular vehicle traffic, up to 40 km/h | 20 | 45 | 0.40 | 20 |
| Pedestrian passages, vehicle turning, loading and unloading points | 50 | 50 | 0.40 | 20 |
How to read these figures
- Maintained illuminance, in lux
- The average light level on the task area that the installation must not fall below at any time in its life. A new installation starts brighter than this figure to allow for light sources dimming with age and for dirt on fittings and room surfaces.
- Uniformity
- The lowest illuminance in the task area divided by the average. A uniformity of 0.6 means the darkest point receives at least 60% of the average.
- Unified glare rating limit
- A measure of discomfort glare from the luminaires as seen by someone in the room. Lower is better. Limits step from 16 for drawing offices through 19 for general offices and 22 to 25 for industrial work, up to 28 for circulation.
- Colour rendering index
- How accurately colours appear under the light source, on a scale to 100. A value of 80 is the minimum for rooms where people work for long periods, and 90 is used where colour is judged.
Figures are from BS EN 12464-1:2011 and BS EN 12464-2:2014. The 2021 edition revises some of them, so confirm against the current edition for your project.
Emergency lighting
Escape lighting comes on when the supply fails. BS 5266-1 says where it is needed and BS EN 1838 sets the levels.
0 lux
minimum along the centre line of an escape route
0 lux
minimum across open areas
0 hours
duration in most premises
Where emergency luminaires go
- At each exit door and outside each final exit
- On stairs, so that each tread receives direct light
- At each change of level and change of direction
- At each intersection of corridors
- At fire alarm call points and firefighting equipment
- At first-aid posts
Testing
A short functional test every month and a full-duration test every year, each recorded in the logbook. Self-testing luminaires do this automatically.
Energy
In England, Approved Document L sets a minimum efficacy for new and replacement lighting and expects controls that stop it running in empty or daylit spaces.
0 lm/W
general lighting, luminaire lumens per circuit-watt
0 lm/W
display lighting, light source lumens per circuit-watt
Glossary
Lumen (lm)
The unit of light output. A luminaire's lumen figure is the total light it emits.
Lux (lx)
The unit of illuminance: one lumen falling on one square metre. It describes the light arriving at a surface.
Candela (cd)
The unit of luminous intensity: how strongly a luminaire emits in one direction. Polar curves are plotted in candela per 1,000 lumens.
Efficacy (lm/W)
Light output divided by electrical input. The higher the figure, the less energy per unit of light.
Maintenance factor
The fraction of initial light output still delivered at the end of the maintenance cycle. A calculation multiplies by it so that the scheme still meets the requirement when the installation is old and dirty.
Working plane
The surface on which illuminance is calculated. Usually desk height, about 0.75 m, or the floor in circulation and storage areas.
Colour temperature (K)
The appearance of white light. Around 3000 K is warm, 4000 K neutral, and 5000 K to 6500 K cool.
Polar curve
A diagram of a luminaire's intensity at each angle from straight down. Its shape shows whether the distribution is narrow or wide.
Photometric file
The measured light distribution of a luminaire in a standard format, IES or EULUMDAT (LDT), used by calculation software.
IP rating
Ingress protection against solids and water, such as IP65. The first digit is dust, the second water.
IK rating
Resistance to mechanical impact, from IK00 to IK10.
DALI-2
The open standard for digital lighting control, in which each luminaire and sensor is individually addressable.
LENI
Lighting Energy Numeric Indicator: the annual lighting energy of a building in kWh per square metre.