Standards and guidance

The standards a lighting scheme is designed to, in plain terms.

Which standards apply

Light levels by sector

Every task has a required light level, uniformity, glare limit and colour rendering. Open a sector to see its figures.

Offices500 lux at the desk, glare limited to UGR 19
Offices: requirements from BS EN 12464-1:2011
Task or areaLuxUGR limitUniformityRa
Filing, copying300190.4080
Writing, typing, reading, data processing500190.6080
CAD workstations500190.6080
Technical drawing750160.7080
Conference and meeting rooms500190.6080
Reception desk300220.6080
Archives200250.4080
Retail and showrooms300 lux on the sales floor, colour rendering of 80 or better
Retail and showrooms: requirements from BS EN 12464-1:2011
Task or areaLuxUGR limitUniformityRa
Sales area300220.4080
Till area500190.6080
Wrapper table500190.6080
Education300 lux in classrooms, 500 lux at the board
Education: requirements from BS EN 12464-1:2011
Task or areaLuxUGR limitUniformityRa
Classrooms, tutorial rooms300190.6080
Classrooms for evening classes and adult education500190.6080
Black, green and white boards500190.7080
Lecture halls500190.6080
Circulation areas, corridors100250.4080
Stairs150250.4080
Warehousing and logistics150 lux in manned aisles, with light on the rack face
Warehousing and logistics: requirements from BS EN 12464-1:2011
Task or areaLuxUGR limitUniformityRa
Store and stock rooms100250.4060
Dispatch, packing and handling areas300250.6060
Storage rack areas: gangways, unmanned20none0.4040
Storage rack areas: gangways, manned150220.4060
Storage rack areas: control stations150220.6080
Loading ramps and bays150250.4040
Manufacturing and assembly200 to 750 lux, set by the finest task on the line
Manufacturing and assembly: requirements from BS EN 12464-1:2011
Task or areaLuxUGR limitUniformityRa
Rough assembly work200250.6080
Medium assembly work300250.6080
Fine assembly work500220.6080
Precision assembly work750190.7080
Welding300250.6060
Rough and average machining, tolerances of 0.1 mm or more300220.6060
Precision machining and grinding, tolerances under 0.1 mm500190.7060
Scribing, inspection750190.7060
Food and drink production200 to 500 lux, in sealed and cleanable fittings
Food and drink production: requirements from BS EN 12464-1:2011
Task or areaLuxUGR limitUniformityRa
Washing, barrel filling, cleaning, sieving, peeling200250.4080
Sorting and washing of products, milling, mixing, packing300250.6080
Cutting and sorting of fruit and vegetables300250.6080
Critical zones in slaughterhouses, butchers and dairies500250.6080
Manufacture of delicatessen foods, kitchen work500220.6080
Product control, inspection of glasses and bottles500220.6080
Colour inspection1,000160.7090
Yards and loading bays5 to 50 lux outdoors, by type of traffic
Yards and loading bays: requirements from BS EN 12464-2:2014
Task or areaLuxGR limitUniformityRa
Walkways exclusively for pedestrians5500.2520
Traffic areas for slowly moving vehicles, up to 10 km/h10500.4020
Regular vehicle traffic, up to 40 km/h20450.4020
Pedestrian passages, vehicle turning, loading and unloading points50500.4020
How to read these figures
Maintained illuminance, in lux
The average light level on the task area that the installation must not fall below at any time in its life. A new installation starts brighter than this figure to allow for light sources dimming with age and for dirt on fittings and room surfaces.
Uniformity
The lowest illuminance in the task area divided by the average. A uniformity of 0.6 means the darkest point receives at least 60% of the average.
Unified glare rating limit
A measure of discomfort glare from the luminaires as seen by someone in the room. Lower is better. Limits step from 16 for drawing offices through 19 for general offices and 22 to 25 for industrial work, up to 28 for circulation.
Colour rendering index
How accurately colours appear under the light source, on a scale to 100. A value of 80 is the minimum for rooms where people work for long periods, and 90 is used where colour is judged.

Figures are from BS EN 12464-1:2011 and BS EN 12464-2:2014. The 2021 edition revises some of them, so confirm against the current edition for your project.

Emergency lighting

Escape lighting comes on when the supply fails. BS 5266-1 says where it is needed and BS EN 1838 sets the levels.

0 lux

minimum along the centre line of an escape route

0 lux

minimum across open areas

0 hours

duration in most premises

Where emergency luminaires go
  • At each exit door and outside each final exit
  • On stairs, so that each tread receives direct light
  • At each change of level and change of direction
  • At each intersection of corridors
  • At fire alarm call points and firefighting equipment
  • At first-aid posts
Testing

A short functional test every month and a full-duration test every year, each recorded in the logbook. Self-testing luminaires do this automatically.

Energy

In England, Approved Document L sets a minimum efficacy for new and replacement lighting and expects controls that stop it running in empty or daylit spaces.

0 lm/W

general lighting, luminaire lumens per circuit-watt

0 lm/W

display lighting, light source lumens per circuit-watt

Glossary

Lumen (lm)

The unit of light output. A luminaire's lumen figure is the total light it emits.

Lux (lx)

The unit of illuminance: one lumen falling on one square metre. It describes the light arriving at a surface.

Candela (cd)

The unit of luminous intensity: how strongly a luminaire emits in one direction. Polar curves are plotted in candela per 1,000 lumens.

Efficacy (lm/W)

Light output divided by electrical input. The higher the figure, the less energy per unit of light.

Maintenance factor

The fraction of initial light output still delivered at the end of the maintenance cycle. A calculation multiplies by it so that the scheme still meets the requirement when the installation is old and dirty.

Working plane

The surface on which illuminance is calculated. Usually desk height, about 0.75 m, or the floor in circulation and storage areas.

Colour temperature (K)

The appearance of white light. Around 3000 K is warm, 4000 K neutral, and 5000 K to 6500 K cool.

Polar curve

A diagram of a luminaire's intensity at each angle from straight down. Its shape shows whether the distribution is narrow or wide.

Photometric file

The measured light distribution of a luminaire in a standard format, IES or EULUMDAT (LDT), used by calculation software.

IP rating

Ingress protection against solids and water, such as IP65. The first digit is dust, the second water.

IK rating

Resistance to mechanical impact, from IK00 to IK10.

DALI-2

The open standard for digital lighting control, in which each luminaire and sensor is individually addressable.

LENI

Lighting Energy Numeric Indicator: the annual lighting energy of a building in kWh per square metre.